Model |
Overspanning |
Onderspanning |
Unbanlance |
Fasevolgorde |
Fasefout |
Resetten |
Test |
PTC-bescherming | Lastbescherming | |||
ZHRV1 |
Instelbereik | Vertragingsbereik | Instelbereik | Vertragingsbereik | Instelbereik | Vertragingsbereik | ||||||
01 | 1.05...1.30 | 0,1s...10s | - | - | - | - | - | + | - | - | - | - |
02 | - | - | 0.70...0.95 | 0,1s...10s | - | - | - | + | - | - | - | - |
03 | 1.05...1.30 | 0,1s...10s | 0.70...0.95 | 0,1s...10s | - | - | - | + | - | - | ○ | ○ |
04 | 1.05...1.30 | 0,1s...10s | 0.70...0.95 | 0,1s...10s | - | - | + | + | - | - | ○ | ○ |
05 | 1.05...1.30 | 0,1s...10s | 0.70...0.95 | 0,1s...10s | 8% | 2 sec. | - | + | - | - | ○ | ○ |
06 | 1.05...1.30 | 0,1s...10s | 0.70...0.95 | 0,1s...10s | 8% | 2 sec. | + | + | - | - | ○ | ○ |
07 | 1.05...1.30 | 0,1s...10s | 0.70...0.95 | 0,1s...10s | 5%...15% | 0,1s...10s | - | + | - | - | ○ | ○ |
08 | 1.05...1.30 | 0,1s...10s | 0.70...0.95 | 0,1s...10s | 5%...15% | 0,1s...10s | + | + | - | - | ○ | ○ |
09 | 1.05...1.30 | 2 sec. | 0.70...0.95 | 2 sec. | 8% | 2 sec. | - | + | - | - | ○ | ○ |
10 | 1.05...1.30 | 2 sec. | 0.70...0.95 | 2 sec. | 8% | 2 sec. | + | + | ○ | ○ | ○ | ○ |
11 | 1.15 | 2 sec. | 0.85 | 2 sec. | 5%...15% | 0,1s...10s | - | + | ○ | ○ | ○ | ○ |
12 | 1.15 | 2 sec. | 0.85 | 2 sec. | 5%...15% | 0,1s...10s | + | + | ○ | ○ | ○ | ○ |
13 | 1.15 | 2 sec. | 0.85 | 2 sec. | 8% | 2 sec. | - | + | ○ | ○ | ○ | ○ |
14 | 1.15 | 2 sec. | 0.85 | 2 sec. | 8% | 2 sec. | + | + | ○ | ○ | ○ | ○ |
15 | 1.15 | 2 sec. | 0.85 | 2 sec. | - | - | - | + | ○ | ○ | ○ | ○ |
16 | 1.15 | 2 sec. | 0.85 | 2 sec. | - | - | + | + | - | - | - | - |
17 | - | - | - | - | 5%...15% | 0,1s...10s | + | + | - | - | - | - |
18 | - | - | - | - | - | - | + | + | - | - | - | - |
19 | - | - | - | - | 8% | 2 sec. | + | + | - | - | - | - |
Nominale voedingsspanning | AC 220 V, AC230, AC240V, AC380 V, AC400V, AC415V |
Nominale voedingsfrequentie | 50 Hz/60 Hz |
Drempelbereik overspanning | (1.05~1.30)*UE |
Drempelbereik onderspanning | (0.70~0.95)*UE |
Drempelbereik onbalans | 5%-15% |
Vertragingsbereik actie | 0,1s-10s |
Fasefout en fasevolgorde | ≤1s |
Fout bij spanningsmeting | ≤1% (hele instelbereik) |
Vertragingsfout | ± 10%+0,1s |
Nauwkeurigheid van de knopinstelling | ±1% schaalwaarde |
Nominale isolatiespanning | 415 V. |
Capaciteit contactconfiguratie(A) | 10 A. |
IP-klasse | IP20 |
Klasse van vervuiling | 3 |
Elektrische levensduur | 105 |
Mechanicall leven | 106 |
Hoogte | ≤2000 m. |
Toegestane relatieve vochtigheid | ≤50% (40 ºC ) (geen condensatie) |
Categorie gebruiken | AC-15 |
Type kortsluitbeveiliging | RT36-00 5 A. |
Contactcapaciteit | UE/le: 240 V/1,5 A, 415 V/0,95 A. |
Uitvoertype | 1C/O |
DIN-railstandaard | Breedte 35 mm (IEC/EN60715) |